Single Phasing Relay (ESR10P) |
Introduction
Single Phasing Relay ESR10P also called Open/Reversed Phase Relay monitors sequence and failure of phase and also voltage reduction in a three phase, three wire supply system.The output relay normally energises when the phases are correct.The relay will release when a phase is lost or phase sequence is reversed, or the voltage is reduced.
Mode of operation
Single Phasing Relay ESR10P is connected to the three phases of the supply system at terminals 1,2 and 3 from which the control supply is also derived. The relay senses the negative sequence voltage of the circuit and normally energises when the phase sequence is correct.The relay will release either for lost phase, or for reversed phase or reduced voltage.
Application
Single Phasing Relay ESR10P is used in three phase motor protection, protection of three phase rectifier and thyristor panels, battery chargers, transformer rectifier units, etc. It is also used in ships, mobile cranes, electric traversers, etc.or anywhere the phase sequence or loss of phase to be safegaurded such as power distribution systems,etc.
Technical Data
|
Supply Voltage VAC : 400/415V
3 Ph 3W AC.
Supply Frequency : 50 - 60 Hz. Permissible Amb. Temp : - 15 to + 55 deg.C. Permissible Voltage variation : - 80 to 110% of V. Permissible frequency variation : - 10 to + 10 % . Maxm.Power consumption : 7.0 VA. Maximum switching frequency : 1000 Cycles/min. Delay on break : 0.5S minimum.
|
Insulation
:
2500V AC for 1 min.
Mechanical Life : 10 million. Terminals : Suitable for 2x2.5 sq.mm. cable. AC Contact Rating : Continuous capacity 6A ( at 250 VAC 50 Hz ) Rated making capacity11A Rated breaking capacity 5A (Resistive) 1.3A (Inductive 0.5 pf.) Mounting : Projection (ELR10P) Weight : 440 gms. |
For Further details please E-mail to us