This site is out of date.  Visit our new website at www.guha.biz

Application

Largest manufacturer of edible oils and fatty acid derivatives in South India
Chilling of vegetable oil fractionation
Capacity 80 TR at -15oC evaporation, -10 to -13oC CaCl2 brine.
Rigid safety standards to be followed due to location near hazardous acetone handling area

The client was considering compressor systems when we were called in.  Guha's engineers opted to use low cost steam from a nearby husk fired boiler.

Comparative utility requirement

Comparison is drawn against compressors that were being considered by the client.

  Compressors Ammonia absorption
Electricity 160 HP installed, consuming 120 KW. 15 HP installed, consuming 9 KW
Heat Nil 800 kg/h steam 

Payback / benefits.

Cost of power - Rs.5/-  ($0.11) per KW.
Effective cost of heat - Rs. 300/- per Ton
Effective saving for 8,000 hrs per year operation - about Rs.2,500,000/- ($56,000/-).
Payback for Ammonia absorption system - Less than 18  months.  
If the cost differential with compressors is taken, payback would be very attractive at around 6 months.